
Lightning Protection 601
impedance rises until it becomes an open circuit with the capacitor fully
charged. For a traveling wave section terminated in a capacitor, the voltage
ramps up to double the voltage as
An inductance initially appears almost as an open circuit. As the inductor
allows more current to flow, its impedance drops until it is equivalent to a
short circuit. For a traveling wave section terminated in an inductor, the
voltage initially doubles then decays down to zero as
A cable section attached to an overhead circuit behaves similarly to a
capacitor. It is like an open-circuited traveling wave section with a low surge
impedance. In fact, a capacitor can be modeled in a traveling wave program
such as EMTP as a traveling wave section with a surge impedance of Dt/2
C and a travel time of Dt/2, where Dt is small (usually the time step of the
simulation) (Dommel, 1986). Likewise, we may model an inductor as a
traveling wave section shorted at the end with a surge impedance equal to
2L/Dt and a travel time of Dt/2.
Corona impacts traveling waves by modifying the surge impedance. When
lightning strikes an overhead distribution circuit, tremendous voltages are
created. The voltage stress on the conductor surface breaks down the air
surrounding the conductor, releasing charge into the air in many small
streamers. A high-voltage transmission line may have a corona envelope of
several feet (1 m), which increases the capacitance. This decreases the surge
impedance and increases coupling to other conductors and slopes off the
front of the wave. Normally, distribution line insulation flashes over before
significant corona develops, so we can neglect corona in most cases.
Predischarge currents, an effect similar to corona, may also form between
conductors. When the voltage between two parallel conductors reaches the
flashover strength of air (about 180 kV/ft or 600 kV/m), a sheet of many
small streamers containing predischarge currents flows between the conduc-
tors. This is a precursor to a complete breakdown. The predischarge current
delays the breakdown and relieves voltage stress between the conductors.
While the predischarge currents are flowing, the resistance across the gap is
400 W/ft or 1310 W/m of line section (Wagner, 1964; Wagner and Hileman,
1963; Wagner and Hileman, 1964). Normally, on overhead distribution cir-
cuits, the weakest insulation is at poles, so in most cases, the circuit flashes
over before the circuit enters the predischarge state. Predischarge currents
do make midspan flashovers less likely and may help with using arresters
to protect lines.
VV e
TI
t
ZC
=-
Ê
Ë
Á
ˆ
¯
˜
-
21
VV e
TI
Z
L
t
=-
Ê
Ë
Á
ˆ
¯
˜
-
21
1791_book.fm Page 601 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC