
576 Electric Power Distribution Handbook
Series capacitors can superbly compensate flicker from fluctuating induc-
tive loads. For resistive loads, series capacitors provide much less benefit.
The voltage drop through the distribution system is approximately I
R
R +
I
X
X. Reducing X with a series capacitor helps reduce the I
X
X term for fluc-
tuating I
X
; but if just I
R
fluctuates, series capacitors provide little benefit.
Electrically, series capacitors elegantly solve voltage flicker; in practice,
they are not widely used, mainly because of
• Reliability of short-circuit protection — Historically, spark gaps were
used to protect the capacitors during downstream faults. Utilities
have had many problems with failures.
• Cost — Series capacitors are nonstandard and must be custom engi-
neered.
• Unusual — Line crews and field engineers find series capacitors
strange. For example, if crews switch in a shunt capacitor down-
stream of a series capacitor, the voltage may go down instead of up.
Increased fault currents downstream of the capacitor can make coor-
dination of protective devices more difficult.
• Ferroresonance — Series capacitors may also ferroresonate with
downstream transformers under the right conditions.
A key design issue is the voltage across the capacitor during faults down-
stream of the unit. During a fault downstream of the series capacitor, the
voltage across the capacitor units is the short-circuit current times the capac-
itor impedance. Depending on the impedances upstream of the capacitor
relative to the capacitor size, the voltage across the series capacitor can
exceed the system’s nominal voltage. When calculating the available fault
current downstream of the capacitor, include the impedance reduction
caused by the capacitor. The fault current normally can rise past the capacitor
(depending on the amount of capacitance relative to the system impedance
and the line X/R ratio). The highest fault current can be some distance from
the capacitor. Figure 11.25 shows an example on a 12.5-kV system for a series
capacitor placed 3 mi from the substation to compensate for a fluctuating
load at 8 mi from the substation. The series capacitor significantly alters the
fault-current profile, and the fault current impresses significant voltage
across the capacitor. Some sort of protection is needed to prevent this.
The increased fault current raises the primary voltage and the customers’
voltage during the fault. Figure 11.26 shows a profile of the line voltages for
a fault at 4.75 mi for the example shown in Figure 11.25. Under this scenario,
the fault current is leading (capacitive), so voltages rise along the line until
the series capacitor. These overvoltages are unacceptable, so some overvolt-
age protection across the capacitor is vital to prevent them. This example
has a rather poor choice of location and impedances, but it illustrates how
important it is to consider these applications carefully. Reducing the imped-
ance of the capacitor reduces the overvoltages and reduces the fault currents.
1791_book.fm Page 576 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC