
558 Electric Power Distribution Handbook
exceeded a voltage THD of 5% (less than 5% of exceeded 4%; 87% had THD
less than 2.5%) (Govindarajan et al., 1991). A few of the sites had current
distortion exceeding IEEE 519 standards. In a large survey of locations on
the Sierra Pacific Power Company, voltage THD averaged 1.59%, and current
THD averaged 5.3% (Etezadi-Amoli and Florence, 1990).
Some work has been done to investigate the impact of new harmonic loads
on the harmonic distortion. Compact fluorescent lights with electronic bal-
lasts, heat pumps and air conditioners with adjustable-speed drives, com-
puters, and electric vehicle battery chargers are some of the loads that could
drive up harmonics. Pileggi et al. (1993) predicted that if every home used
two or three electronically ballasted fluorescent lights, voltage distortion may
exceed 5%. This is hard to believe, but it does make us consider the impact
of future electronic loads. Dwyer et al. (1995) also came to similar conclu-
sions: modest numbers of electronic compact fluorescent lights (50 W per
house) can raise the voltage distortion above 5%, especially if feeder capac-
itors create resonances that amplify the harmonics. It helps that multiple
single-phase loads have some phase-angle cancellation; harmonic loads do
not necessarily sum linearly (Mansoor et al., 1995).
In the northeastern U.S., Emanuel et al. (1995) predict rising levels of
harmonic distortion based on predictions of increased use of adjustable-
speed drives, electronic fluorescent lights, computer loads, and other non-
linear loads. They predict that more nonlinear loads can add as much as
0.3% per year to the voltage THD under the worst-case scenario. A limited
number of measurements by the same group of researchers over a 10-year
time period found that harmonic voltages have increased at a rate of about
0.1% per year (it takes 10 years for the THD to increase by a percentage
point) (Nejdawi et al., 1999).
Penetrations of air conditioners driven by adjustable-speed drives to 10 to
20% can raise voltage THD levels above 5% (Gorgette et al., 2000; Thallam
et al., 1992). In another study, Bohn (1996) predicted that electric-vehicle
battery charger penetration levels as low as 5% could increase voltage THD
above 5%, especially on weak systems. In both of these cases, investigators
found wide differences in equipment designs. Some generate much more
harmonics than others. For example, some adjustable-speed drives with more
sophisticated rectifier sections cause much less harmonics than standard
rectifiers. As electronic loads grow, utilities must involve themselves in set-
ting guidelines to limit the harmonics introduced by end-use equipment.
Finding the source of harmonics can be tricky — IEEE 519A provides two
ways to track down harmonics (IEEE P519A draft 7, 2000):
1. Time variations — If harmonics are intermittent, correlating the time
variations of the voltage or current harmonics with the operation
time of facilities or of specific equipment can identify the harmonic
producer.
2. Monitoring with capacitor banks off — In a radial circuit with no capac-
itors, harmonic sources inject current that flows back to the power
1791_book.fm Page 558 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC