
612 Electric Power Distribution Handbook
a low estimate of the true failure rate; arresters are almost a throw-away
commodity; not all failures are returned. Arresters may also fail without
utilities noticing; if the isolator operates and a circuit breaker or recloser
closes back in, the failed arrester is left with a dangling lead that may not
be found for some time. Ontario Hydro (CEA 160 D 597, 1998) has recorded
failure rates averaging about 0.15% in a moderately low-lightning area
with about one flash/km
2
/year. About 40% of their arrester failures
occurred during storm periods.
Lightning arresters fail for a variety of reasons. Moisture ingress, failure
due to lightning, and temporary overvoltages beyond arrester capability
are some of the possibilities. Early in my career, I was involved with lab
tests of arresters and EMTP modeling to evaluate system conditions such
as ferroresonance, presence of distributed generation, and regulation volt-
ages (Short et al., 1994). The main conclusion was that well-made arresters
should perform well. More problems were likely for tightly applied arrest-
ers (such as using a 9-kV duty-cycle arrester with a 7.65-kV MCOV on a
12.47/7.2-kV system), so avoid tightly applying arresters under normal
circumstances.
Darveniza et al. (2000) inspected several arresters damaged in service in
Australia. Of the gapped metal-oxide arresters inspected, both polymer and
porcelain-housed units, moisture ingress caused most failures. Of the gapless
metal-oxide arresters inspected, several were damaged under conditions that
were likely ferroresonance — arresters on riser poles with single-pole switch-
ing or with a cable fault. Another portion were likely from severe lightning,
most likely from multiple strokes. Most of the failures occurred along the
outer surface of the blocks. A small number of metal-oxide arresters, both
polymer and porcelain, showed signs of moisture ingress damage, but over-
all, the metal-oxide arresters had fewer problems with moisture ingress than
might be expected.
Lightning causes some arrester failures. Figure 12.15 shows an example.
The standard test waves (4/10 msec or 8/20 msec) do not replicate lightning
very well but are assumed to test an arrester well enough to verify field
performance. The energy of standard test waves along with the charge is
shown in Table 12.6. Charge corresponds well with arrester energy input
since the arrester discharge voltage stays fairly constant with current.
Studies of surge currents through arresters show that individual arresters
only conduct a portion of the lightning current. Normally, the lightning
current takes more than one path to ground. Often that path is a flashover
caused by the lightning; the flashover is a low-impedance path that “pro-
tects” the arrester. The largest stroke through an arrester measured during
an EPRI study with more than 200 arrester years of monitoring using light-
ning transient recorders measured 28 kA (Barker et al., 1993). During the
study, 2% of arresters discharged more than 20 kA annually. The largest
energy event was 10.2 kJ/kV of MCOV rating (the arrester did not fail, but
larger than normal 4.7-cm diameter blocks were used).
1791_book.fm Page 612 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC