LINE PROTECTION WITH OVERCURRENT RELAYS 261
increase the operating time too much. It may be that the CT ratio and the relay’s range of
adjustment do not permit adjusting for so low a multiple of pickup; in that event the only
recourse, aside from changing the CT or the relay, is to use the highest possible pickup for
which the relay can be adjusted.
To assure selectivity under all circumstances, the pickup of a given relay should be
somewhat higher than that of other relays nearer to the fault and with which the given
relay must be selective.
Because the impedance of generators increases from subtransient to synchronous as time
progresses from the instant that a short circuit occurs, the question naturally arises as to
which value of impedance to use in calculating the magnitude of short-circuit current for
protective-relaying purposes where overcurrent relaying is involved. The answer to this
question depends on the operating speed of the relay under consideration, on the amount
by which generator impedance affects the magnitude of the short-circuit current, and on
the particular relay setting involved. Usually, the impedance that limits the magnitude of
the short-circuit current contains so much transformer and line impedance that the effect
of changing generator impedance is negligible; one can always determine this effect in any
given application. For relays near a large generating station that furnishes most of the
short-circuit current, synchronous impedance would be best for determining the pickup of
a relay for back-up purposes particularly if the operating time of the relay was to be as long
as a second or two. On the other hand, the pickup of a high-speed relay near such a
generating station would be determined by the use of transient–or possibly even
subtransient–impedance. Ordinarily, however, transient impedance will be found most
suitable for all purposes–particularly for subtransmission or distribution circuits where
overcurrent relays are generally used; there is enough transformer and line impedance
between such circuits and the generating stations so that the effect of changing generator
impedance is negligible. In fact, for distribution circuits, it is frequently sufficiently
accurate to assume a source impedance that limits the current to the source-breaker
interrupting capacity on the high-voltage side of a power transformer feeding such a
circuit; in other words, only slightly more total impedance than that of the transformer
itself and of the circuit to be protected is assumed.
Whether to take into account the effect of arc and ground resistance depends on what one
is interested in. Arc resistance may or may not exist. Occasionally, a metallic fault with no
arcing may occur. When one is concerned about the maximum possible value of fault
current, he should assume no arc resistance unless he is willing to chance the possibility of
faulty relay operation should a fault occur without resistance. Thus, as will be seen later,
for choosing the pickup of instantaneous overcurrent relays or the time-delay adjustment
for inverse-time relays, it is more conservative to assume no arc resistance.
When one is choosing the pickup of inverse-time relays, the effect of arc resistance should
be considered. This is done to a limited extent when one arbitrarily chooses a pickup
current lower than the current at which pickup must surely occur, as recommended in the
foregoing material; however, this pickup may not be low enough. In view of the fact that
an arc may lengthen considerably in the wind, and thereby greatly increase its resistance,
it is a question how far to go in this respect. At least, one should take into account the
resistance of the arc, when it first occurs, whose length is the shortest distance between
conductors or to ground. Beyond this, what one should do depends on the operating time