180 Practical Variable Speed Drives and Power Electronics
The correct procedure is:
• The first step is to select a correctly rated electric motor
• Only when this is completed, a suitable AC converter is chosen to match the
requirements of the motor
From the motor point of view, the main factors which need to be considered are the
motor power rating (kW), the number of poles (speed) and the frame size so that the load
torque on the motor shaft remains within the continuous torque capability of the motor at
all speeds within the speed range. High torques of short duration, such as starting torque,
can usually be easily accommodated within certain limits outlined below.
:NKRUGJGHOROZ_ULIUT\KXZKXLKJYW[OXXKRIGMKSUZUXY
When selecting an AC motor for any drive application, the most important requirement is
to ensure that the motor does not become overloaded or stall under all circumstances of
speed and load, i.e. over the entire speed range.
To stay within the temperature rise limits of the motor, the torque required by the load
for starting, acceleration and for continuous running must be within the rated output
torque capacity of the motor.
For AC motors connected to the power supply direct-on-line (DOL), it is usually
sufficient to ensure that load torque is sufficiently below motor torque at the rated speed
of the motor, for example the torque at 1450 rev/m on a 4 pole motor. These fixed speed
drives operate only at one speed. It may also be necessary to ensure that the starting
torque of the motor is higher than the breakaway torque of the load.
In the case of a variable speed drive, the load torque usually changes with speed, so it is
essential to check that the motor torque exceeds the load torque at all speeds in the speed
range. For example, a centrifugal pump has a variable torque characteristic, where the
starting torque is low and the torque increases as the square of the speed as shown in
Figure 7.6. Other loads, such as a conveyor, may have a constant torque characteristic,
where the load torque remains constant for all speeds, as shown in Figure 7.7.
The continuous load torque capacity (loadability) of a standard TEFC squirrel cage
induction motor used with VVVF converters is always lower than the rated torque of the
motor itself for the following reasons:
• At all speeds, the load capacity is reduced as a result of additional heating in
the motor caused by harmonic currents, however small. These occur because
the output current waveform of the converter is not completely sinusoidal,
even with modern PWM inverters with switching frequencies around 10 kHz.
Traditionally, a de-rating of between 5% and 10% was used, depending on the
type of motor (number of poles) and the type of converter. But, it has become
common practice with modern PWM inverters to make provision for no de-
rating at all. This relies on the fact that modern IEC motors always have a
built-in thermal reserve (refer to Chapter 2), which will accommodate any
additional heating. Also, the mechanical load is seldom exactly equal to the
motor rating and is often lower by as much as 20%.
It is considered good engineering practice to allow a small margin of safety,
so a de-rating of up to 5% is usually provided.