
W
uodern Power system
Analysis
I
AF@lap,{s):o:
rt v(
ttsgttf t^ps
AD
xu'c
(8.18)
s
(1+
T,rs)(l*
4s)
I
4,flr*uoyro,":
I
AP',:g
xl-
_t
(1
K
\
I
-l
rl
p,
/R
AP,
*
zors)
+
KseKt
KreKrKp,
+ K.sKtKps
/ R
(8.1e)
(8.20)
If
KrrK,
=l
Ar=
(
|
\rc"
"
\
B+llR)
If the speed
changer setting is changed
by
AP, while
the load demand
changes by APo, the
steady frequency
change
is obtained by superposition,
i.e.
(8.21)
According to
Eq.
(8.2I)
the frequency
change
caused by
load demand
can be
compensated by
changing
the setting of the
speed
changer, i.e.
APc-
APo, for Af
=
Q
Figure
8,7
depicts
two load
frequency
plots-one
to
give
scheduled
frequency at I00Vo
rated
load and the other
to
give
the same frequency
at
6O7o
rated
load.
A 100 MVA synchronous
generator
operates
on full
load at at frequency
of 50
Hz.
The load is suddenly
reduced to 50 MW. Due
to time
lag in
governor
system, the steam
valve begins
to close after 0.4 seconds.
Determine
the
change
in
frequency that occurs
in this time.
Given
H
=
5
kW-sec/kVA
of
generator
capacity.
Solution
Kinetic
energy stored in
rotating
parts
of
generator and turbine
=
5
x
100
x
1.000
=
5
x
105
kW-sec
Excess
power
input
to
generator
before
the steam
valve
begins
to
close
=
50
MW
Excess energy input
to rotating
parts
in 0.4
sec
=
50
x
1,000
x
0.4
=
20,000
kW-sec
Stored
kinetic
energy oo
(frequency)2
Frequency
at the end of 0.4
sec
=
5o
x
I
soo,ooo
+
zo,ooo
)t"=
5r
rfz
\
500,000
)
Ar
=
(
".
ru)
'o"
-
APo)
Autor"tic
G"n"r"tion
and
Volt"g"
Conttol
F
Two
generators rated
200
MW and
400 MW
are operating
in
parallel.
The
droop
characteristics
of
their
governors
are 4Vo and 5Vo,
respectively from
no
load
to full
load.
Assuming
that
the
generators are operating
at 50
Hz
at
no
load,
how
would a
load
of 600
MW be
shared
between
them?
What will be
the
system
frequency
at this
load?
Assume
free
governor
operation.
Repeat
the
problem if
both
governors have
a droop
of 4Vo.
Solution
Since
the
generators are in
parallel,
they will
operate
at the same
frequency
at
steady
load.
Let load
on
generator 1
(200
MW)
=
x MW
and
load
on
generator 2
(400
MW)
=
(600
-
x)
MW
Reduction
in
frequency
=
Af
Now
af_
x
af
600-x
Equating
Af
in
(i)
and
v-
600-
x=
System
frequency
=
50
-
0'0-1150
x
231
=
47 .69
Hz
'
200
It is observed
here
that
due
to difference
in
droop characteristics
of
governors,
generator
I
gets
overloaded
while
generator
2 is
underloaded.
It easily
follows
from
above
that if both
governors
have
a droop of.4Vo, they
will
share
the load
as
200 MW
and
400
MW respectively,
i.e. they are loaded
corresponding
to
their
ratings.
This indeed
is desirable
from operational
considerations.
Dynamic
Response
To
obtain
the dynamic
response
giving the
change in frequency
as
function of
the
time
for a
step
change
in load,
we must
obtain the
Laplace inverse
of
Eq.
(8.14).
The
characteristic
equation
being
of
third order,
dynamic
response
can
r' r | 1-!-- - I f-,- - -^^^tC: ^ ---*^-:^^1 ^^^^ tI^.-,^,,^- +L^ ^L^-^^+^--i^+in
Onfy
Dg ODIalneU
luf
A SPtrUfffU
ll|'llll('llua1'I
Ua1DE.
II(rwsYsIr LfIs
r,Il<ll4ivLsllDrlv
equation
can be
approximated
as first
order
by examining
the relative
magnitudes
of
the
time
constants
involved.
Typical
values of the time constants
of
load
frequency
control
system
are rdlated
as
0.04
x
50
200
0.05
x
50
400
(ii),
we
get
231
MW
(load
on
generator
-/A trltf /1 ^-l ^-
JOy
lvlw (IUau
ull
Btrrltrriltur
(i)
(ii)
r)
L)