700
SECTION
4
PLC Process
Applications
Industrial Text & Video Company 1-800-752-8398
www.industrialtext.com
CHAPTER
15
Process Controllers
and Loop Tuning
The term Hc
(s)
represents the controller’s transfer function, while the term
Hp
(s)
represents the process’s transfer function. The process’s transfer func-
tion may take the form of a first-order response or a second-order response
(overdamped, underdamped, or critically damped). As we will discuss later,
the ideal controller transfer function for a system with a second-order
process plus lag and dead time is one with proportional, integral, and
derivative (PID) components.
A closed-loop system’s response to a proportional controller creates an error
that cannot be eliminated. This error is referred to as offset. Figure 15-32
shows the graph of a proportional controller’s transfer function, in which a
50% CV output keeps the process variable at the set point. If a load
disturbance occurs, the error will increase and the controller will change the
output variable to try to bring the error back to zero. However, if the load
disturbance requires a permanent output change in the controller (CV
new
), the
one-to-one relationship between the controller and error will prohibit a zero
error value, because the original function curve is changed. For instance, if
the process variable in Figure 15-33a increases due to a load disturbance,
the control variable (assuming a direct-acting controller) will increase pro-
portionally to try to bring the error back to zero. If the load disturbance causes
a permanent change in the required controller output, the new output level
(CV
new
) will cause the process variable to return to the set point value.
However, as PV begins to approach the set point (see Figure 15-33b), the
controller will reduce its output because the error is diminishing. The reduced
CV output will cause the error to increase, because the process requires a
control variable output at the level of CV
new
to maintain the process variable
at the set point. Thus, error will always be present in the system.
100%
50%
0%
CV
new
%
CV
PV
min
PV
max
SP
=
PV
Change in output due
to load disturbance
Hc
EP
CV
PV
SP
+
–
Σ
Load
Disturbance
Hp
Figure 15-32. An offset caused by a load disturbance in a closed-loop system.
In process applications, the need for a permanent change in CV is typical,
thus proportional controllers always produce a small amount of error. This
error limits the use of proportional controllers to applications that include a