144
SECTION
2
Components
and Systems
Industrial Text & Video Company 1-800-752-8398
www.industrialtext.com
CHAPTER
6
The Discrete
Input/Output System
The maximum capacity of this system is 512 inputs or 512 outputs, or a total
combination of 512 inputs and outputs that do not overlap addresses. The 512
possible inputs come from the following word addresses:
Again, note that the capacity is a total of 512 inputs and outputs together, not
512 each. If one input module takes a slot in the input table, the mirror image
slot in the output table is taken by those inputs. The same applies for output
modules.
For instance (see Figure 6-9), if a 4-point output module (see Figure 6-9b) is
placed in rack 0, slot 0 (terminal addresses 0–3), the output table word 000
8
,
bits 0–3, represented by the shaded area in Figure 6-9c, will be mapped for
outputs. Consequently, the input table image corresponding to the slot
location 100
8
, bits 0–3 (represented by the word taken) will not have a mapped
reference input, since it has already been taken by outputs. If an 8-point input
module is used in rack 0, slot 2 (see Figure 6-9a), indicating word location
102
8
(input = 1), the whole eight bits of that location in the input table (location
102
8
bits 0–7) would be taken by the mapping; the corresponding address in
the output table (word location 002
8
, bits 0–7 in Figure 6-9c) would not be able
to be mapped. The bits from the output table that do not have a mapping due
to the use of input modules could be used as internal outputs, since they cannot
be physically connected output field devices (e.g., bits 4–7 of word 000).
For example, in Figure 6-9c, output addresses 0004 through 0007
(corresponding to word 000, bits 4–7 in the I/O table) cannot be physically
connected to an output module because their map locations are taken by an
input module (at word 100, bits 4–7). Therefore, these reference addresses can
only be used as internal coil outputs. The use of these output bits as internal
outputs is shown in Figure 6-10, where output 0004 (now used as an internal
coil) will be turned ON if its logic is TRUE and contacts from this output can
be used in other output rungs.
While the 512 possible outputs come from word addresses:
1000
8
(word 100, bit 0)
•
512 input addresses •
(64 words × 8 bits/word) to
•
•
1777
8
(word 177, bit 7)
0000
8
(word 000, bit 0)
•
512 output addresses •
(64 words × 8 bits/word) to
•
•
0777
8
(word 077, bit 7)