Chapter 5
Equivalent circuits and parameters of power system plant
5-9
5.11 DIRECT AND QUADRATURE AXIS VALUES
The transient reactance is associated with the field winding
and since on salient pole machines this is concentrated on the
direct axis, there is no corresponding quadrature axis value.
The value of reactance applicable in the quadrature axis is the
synchronous reactance, that is
X’
q
= X
q
.
The damper winding (or its equivalent) is more widely spread
and hence the sub-transient reactance associated with this has
a definite quadrature axis value
X”
q
, which differs significantly
in many generators from
X”
d
.
5.12 EFFECT OF SATURATION ON MACHINE
REACTANCES
In general, any electrical machine is designed to avoid severe
saturation of its magnetic circuit. However, it is not
economically possible to operate at such low flux densities as
to reduce saturation to negligible proportions, and in practice a
moderate degree of saturation is accepted.
Since the armature reaction reactance
X
ad
is a ratio AT
ar
/AT
e
it is evident that
AT
e
does not vary in a linear manner for
different voltages, while
AT
ar
remains unchanged. The value
of
X
ad
varies with the degree of saturation present in the
machine, and for extreme accuracy should be determined for
the particular conditions involved in any calculation.
All the other reactances, namely
X
L
, X’
d
and X”
d
, are true
reactances and actually arise from flux leakage. Much of this
leakage occurs in the iron parts of the machines and hence
must be affected by saturation. For a given set of conditions,
the leakage flux exists as a result of the net m.m.f. which
causes it. If the iron circuit is unsaturated its reactance is low
and leakage flux is easily established. If the circuits are highly
saturated the reverse is true and the leakage flux is relatively
lower, so the reactance under saturated conditions is lower
than when unsaturated.
Most calculation methods assume infinite iron permeability
and for this reason lead to somewhat idealised unsaturated
reactance values. The recognition of a finite and varying
permeability makes a solution extremely laborious and in
practice a simple factor of approximately 0.9 is taken as
representing the reduction in reactance arising from
saturation.
It is necessary to distinguish which value of reactance is being
measured when on test. The normal instantaneous short-
circuit test carried out from rated open-circuit voltage gives a
current that is usually several times full load value, so that
saturation is present and the reactance measured is the
saturated value. This value is also known as the 'rated voltage'
value since it is measured by a short circuit applied with the
machine excited to rated voltage.
In some cases, the test may be made from a suitably reduced
voltage so that the initial current is approximately full load
value. This may be the case where the severe mechanical
strain that occurs when the test is performed at rated voltage
has to be avoided. Saturation is very much reduced and the
reactance values measured are virtually unsaturated values.
They are also known as 'rated current' values, for obvious
reasons.
5.13 TRANSFORMERS
A transformer may be replaced in a power system by an
equivalent circuit representing the self-impedance of, and the
mutual coupling between, the windings. A two-winding
transformer can be simply represented as a 'T' network in
which the cross member is the short-circuit impedance, and
the column the excitation impedance. It is rarely necessary in
fault studies to consider excitation impedance as this is usually
many times the magnitude of the short-circuit impedance.
With these simplifying assumptions a three-winding
transformer becomes a star of three impedances and a four-
winding transformer a mesh of six impedances.
The impedances of a transformer, in common with other plant,
can be given in ohms and qualified by a base voltage, or in per
unit or percentage terms and qualified by a base MVA. Care
should be taken with multi-winding transformers to refer all
impedances to a common base MVA or to state the base on
which each is given. The impedances of static apparatus are
independent of the phase sequence of the applied voltage; in
consequence, transformer negative sequence and positive
sequence impedances are identical. In determining the
impedance to zero phase sequence currents, account must be
taken of the winding connections, earthing, and, in some
cases, the construction type. The existence of a path for zero
sequence currents implies a fault to earth and a flow of
balancing currents in the windings of the transformer.
Practical three-phase transformers may have a phase shift
between primary and secondary windings depending on the
connections of the windings – delta or star. The phase shift
that occurs is generally of no significance in fault level
calculations as all phases are shifted equally. It is therefore
ignored. It is normal to find delta-star transformers at the
transmitting end of a transmission system and in distribution
systems for the following reasons:
x At the transmitting end, a higher step-up voltage ratio
is possible than with other winding arrangements,
while the insulation to ground of the star secondary
winding does not increase by the same ratio.
© 2011 Alstom Grid. Single copies of this document may be filed or printed for personal non-commercial use and must include this
copyright notice but may not be copied or displayed for commercial purposes without the prior written permission of Alstom Grid.