
//INTEGRAS/KCG/P AGIN ATION/ WILEY /WPS /FINALS_1 4-12- 04/0470855088_ 26_CHA25 .3D – 572 – [555–586/32]
17.12.2004 10:50PM
25.6.5 Protection system model
The goal of the protection system is to protect the wind turbine from damage caused by
the high currents that can occur when the terminal voltage drops as a result of a short
circuit in the grid. It also has the task of preventing islanding. Islanding is a situation in
which a part of the system continues to be energised by distributed generators, such as
wind turbines, after the system is disconnected from the main system. This situation
should be prevented because it can lead to large deviations of voltage and frequency
from their nominal values, resulting in damage to grid components and loads. It can
also pose a serious threat to maintenance staff, who incorrectly assumes that the system
is de-energised after the disconnection from the transmission system.
The thermal time constants of semiconductor components are very short. Therefore,
the converter that feeds the rotor winding is easily damaged by fault currents, and
overcurrent protection is essential for the converter. The generator itself is more capable
of withstanding fault currents and is therefore less critical. The working principle of
overcurrent protection is as follows. When a voltage drop occurs, the rotor current
quickly increases. This is ‘noticed’ by the controller of the rotor side of the power
electronics converter. Then the rotor windings are shorted using a ‘crow bar’ (basically
turning the generator into a squirr el cage induction generator). A circuit braker between
the stator and the grid is operated and the wind turbine is completely disconnected. The
grid side of the converter can also ‘notice’ the volta ge drop and the corresponding
current increase, depending on the converter controls. After the voltage is restored, the
wind turbine is reconnected to the system.
The anti-islanding protection of the wind turbine acts in response to voltage and/or
frequency deviations or phase angle jumps. The grid side of the converter measures the
grid voltage with a high sampling frequency. There are criteria implemented in the
protection system for determining whether an island exists. If these criteria are met, the
wind turbine is disconnected. The criteria that are applied are a trade-off between the
risk of letting an island go undetected, on the one hand, and of incorrectly detecting an
island when there is none, leading to ‘nuisance tripping’, on the other.
The response of a doubly fed induction generator to a terminal voltage drop is a high-
frequency phenomenon. It cannot be modelled adequately with PSDS software. This
becomes clear when we look at the assumptions on which these programs are based (see
Section 25.2 and Chapter 24). Hence, if the protection system that is incorporated into a
doubly fed induction generator model is used in PSDS it will react to terminal voltage and
not to rotor current. It is thus a simplified representation of the actual protection system.
There are simulations in the literature that show the different responses of reduced-
order and complete models (Akhmatov, 2002). However, presently there are no quanti-
tative investigations that analyse the importance of the differences between the reduced-
order model and the complete mod el for the interaction with the system. The latter is,
however, the main point of interest in PSDS, so this topic requires further investigation.
Further, it must be noted that the protection system of a model of a doubly fed
induction generator that will be used in PSDSs can incorporate criteria only with respect
to the amplitude and frequency of the terminal voltage. As only the effective value of
fundamental harmonic components is studied, it will not be possible to detect phase
jumps.
572 Reduced-order Modelling of Wind Turbines