
//INTEGRAS/KCG/PAGINATION/WILEY/WPS/FINALS_14-12-04/0470855088_06_CHA05.3D – 89 – [79–96/18] 20.12.2004
7:30PM
reduce the increase of network losses. It is possible, with clever control and allowing
overcompensation at high load and low wind conditions, to achieve a net reduction in
grid losses. To assess this, repeated load flow analyses need to be conducted, taking
properly into account the expected distribution of consumption and wind power pro-
duction during the year [e.g. by probabilistic load flow, as in Hatziargyriou, Karakat-
sanis and Papadopoulos (1993) and in Tande and Jø rgensen (1996)].
5.3.4 Flicker
Flicker and/or rapid voltage changes are commonly due to rapid changes in the load or
to switching operations in the system. According to EN 50160, a rapid voltage change
should generally be less than 5 % of U
n
, though a change of up to 10 % of U
n
may occur
several times a day under certain circumstance s.
The flicker severity can be given as a short-term value, P
st
, measured over a period of
10 minutes, or as a long-term value, P
lt
, corresponding to a period of 2 hours, calculated
from a sequence of P
st
values:
P
lt
¼
X
12
i¼1
P
3
st;i
12
!"#
1=3
: ð5:4Þ
According to EN 50160, the long-term flicker severity has to be less than or equal to 1
during 95 % of a week. It is noted that reaction to flicker is subjective, so that in some
cases people may be annoyed by P
lt
¼ 1, for instance, whereas in other cases higher
values can be accepted.
To ensure P
lt
1 at the customer inlets, each source of flicker connected to the
network can be allowed only a limited contribution; for example, in the example
network, E
Pst
¼ 0:7 and E
Plt
¼ 0:5 at the PCC of the wind farm, where E
Pst
and E
Plt
are the short-term and long-term flicker emission limits, respectively. In other networks,
different values may be found by using IEC 61000-3-7 (IEC, 1996b) as a guide.
Wind turbines emit flicker as a result of switching operations, such as startups, and as
a result of rapid fluctuations in the output power during continuous operation.
Following the recommendations in IEC 61400-21, the flicker emission from a single
wind turbine or wind farm may be assessed. Procedures are given for assessing flicker
emission due to switching operations and due to continuous operation.
5.3.4.1 Switching operations
The procedure for assessing flicker emission due to switching operations assumes that
each wind turbine is characterised by a flicker step factor, k
f
(
k
), which is a normalised
measure of the flicker emission due to a single worst-case switching operation. The
worst-case switching ope ration is commonly a startup, although IEC 61400-21 also
requires the assessment of switching operations between gen erators (e.g. to obtain two-
speed operation), if applicable to the wind turbine in question. Further, the procedure
assumes that, for each wind turbine, information is given on the maximum number of
starts, N
10
and N
120
, that can be expected within a 10-minute and 2-hour period,
Wind Power in Power Systems 89