pump of solar collector system started, till the temperature
difference lower to 2ć,the pump stopped. The freeze
protection of the system is drain back system, while the
pump of solar collector system stopped, the water in solar
collectors and pipes drained back into concrete tank.
When the water temperature in the concrete tank is more
than 50ć, the solar heating system directly supply energy
into building for space heating. When the temperature of
the return water from the heating system is higher than 45
ćand lower than 30ć, the heat pump heat the water into
required temperature to meet the heat demand. When return
temperature is lower than 30ć, the solar collector system
store the heat in the concrete tank.
4.1.2 Summer
The ground-source heat pump supply cool water for air
conditioning. The solar collector system is controlled with
the same in heating season. The solar collector system store
the heat in the concrete tank for space heating in Winter,
when the temperature in the concrete tank is higher than
95 ć, the pump of solar collector system stopped.
4.1.3 Other Season
The solar collector system is controlled with the same in
heating season. The solar collector system store the heat in
the concrete tank for space heating in Winter , when the
temperature in the concrete tank is higher than 95 ć, the
pump of solar collector system stopped.
4.2 South Part
In the heating season, solar heating system and
ground-source heat pump system supply energy for space
heating together. In Summer, the solar heating system
supply the heat to absorption refrigerator to cool water for
air conditioning, when the radiation is not enough to
produce higher temperature water, the ground-source heat
pump system started.
4.2.1 Heating Season
The control strategy of solar system is the same with the
North Part in heating season. The freeze protection of the
system is anti-freeze circulation system, when the
temperature in the top part of solar collector system is
lower than 5ć, the pump of solar collector system started,
when temperature increased to 10 ć,the pump system
stopped, part of water in solar collectors and pipes drained
back into heat storage tank.
When the water temperature in the heat storage tank is
more than 50ć, the solar heating system directly supply
energy into building for space heating. When the
temperature of the return water from the heating system is
higher than 45ćand lower than 30ć, the heat pump heats
the water into required temperature to meet the heat
demand. When return temperature is lower than 30ć, the
water heated by solar system go into the evaporator of the
heat pump to improve the efficiency of heat pump for
saving more conventional energy such as electrical power.
4.2.2 Summer
The solar collector system is controlled with the same in
heating season. When the temperature in heat store tank is
more than 88ć,the pump start ,and the absorption refrigerator
started to cool the water in the cooling storage tank.
When the temperature in the top part of cooling storage
tank is lower than the return water temperature, the pump for
supply cooling started. The solar assisted air- conditioning
system and the ground heat pump are parallel operating.
When the return water temperature is lower than the
temperature in the bottom part of cooling storage tank, this
means the cooling demand is less.
Firstly, the absorption refrigeration system cools the water
in the cooling storage tank, when the temperature in which
meet the design requirement, the absorption refrigeration
system stopped.
Then, the solar collector system heat the water in the heat
storage tank. When the temperature in the heat storage tank is
higher than 95ć, the pump for solar collector system stopped.
4.2.3 Other Season
In spring, the solar system and ground pump system supply