68 SECTION 1 Basic Electricity
Figure 6–5
Equipment nameplate. (Source: Delmar/Cengage Learning)
means, branch circuit conductors, controller, short
circuit protective device, and ground fault protec-
tive device. NEC
®
Section 440.32 states that for a
single motor compressor, the branch circuit con-
ductors shall have an ampacity not less than 125%
of either the motor compressor rated load current
or the branch circuit selection current, whichever
is greater. As a general rule the branch circuit
selection current will be greater than the compres-
sor rated load amps because the selection current
includes any indoor and/or outdoor fans.
Termination Temperature
Another factor that must be taken into consider-
ation is the temperature rating of different termina-
tions. The termination is the point of attachment
for conductors such as circuit breakers, disconnects,
switches, and so forth. NEC
®
Section 110.14(C) basi-
cally states that the temperature rating of the termi-
nation cannot be exceeded. Although a wire with a
higher temperature rating may be used, the ampacity
of the wire must be selected on the basis of the lowest
temperature rating in the circuit. Type THHN insula-
tion has a temperature rating of 90°C, but assume
that it is connected to a device with a temperature
rating of 75°C. The ampacity of the wire would have
to be selected on the basis of 75°C, not 90°C.
Occasionally the temperature rating of a device
will be listed on the device or in the manufacturer’s
literature, but as a general rule it is not known. For
this reason, the National Electrical Code
®
states that
conductors for circuits rated at 100 amperes or less
will be selected from the 60°C column, and con-
ductors rated over 100 amperes are to be selected
from the 75°C column. An exception to this is if the
insulation type is rated less than 75°C as is the case
with type TW and UF. If either of these two types of
insulation are employed, the ampere rating of the
conductor must be determined from the 60°C col-
umn regardless of the circuit current.
EXAMPLE
Assume that an equipment nameplate lists the rated
load amps (RLA) of the compressor at 14.8 amps
and the circuit selection current at 22 amps. To
determine the correct conductor size for this unit,
multiply the larger of the two rating by 125%.
22 ⫻ 1.25 ⫽ 27.5 amps
The next step is to determine the conductor size from
NEC
®
Table 310.16. It will be assumed that cop-
per conductors with type THWN insulation will be
used for this installation. Although THWN insula-
tion is located in the 75°C column, the conductor
size will be selected from the 60°C column because
the total circuit current is less than 100 amperes.
Table 310.16 indicates a #10 AWG conductor is the
closest size without going under 27.5 amperes. A #10
AWG conductor will be used for this installation.
The National Electrical Code
®
also requires that a
disconnecting means be located within sight from
and readily accessible to the air conditioning or
refrigeration equipment, Figure 6–6. The NEC
®
does
permit the disconnect to be installed on or within
the equipment provided it is not installed on a panel
that is designed to allow access to the equipment.
The disconnect may be located away from the air
conditioning or refrigeration equipment provided
there is a working clearance of at least 30 inches
to allow service accessibility. This is to enable the
service technician to disconnect power from the unit
without having to enter the building to nd the main