This parameter defines the control time between two successive Upload/Download
functions. If this time expires the access protection is deactivated. The
previously transferred data are invalid.
Type: Unsigned16
Time base: 1ms
Add_Offset:
This parameter identifies the offset in bytes to the begin of the area which is
specified by the Area_Code.
Type: Unsigned16
Data:
This parameter contains the area data to be transferred.
Type: Octet String
Length: 1 to 240
Data_Len:
The parameter defines the length of the requested data.
Type: Unsigned8
Range: 1 to 240
Status:
The parameter Status indicates success or failure of the function.
Possible values:
DDLM_Start_Seq: OK,DS,NA,RS,RR,UE,TO,FE,RE,NE,AD,IP,NI,
SE,SC,EA,LE,RE
DDLM_Download: OK,DS,NA,RS,RR,UE,TO,FE,RE,NE,AD,EA,LE,SC,NI,NC
DDLM_Upload: OK,DS,NA,RS,RR,UE,TO,FE,RE,NE,EA,LE,NI,SC,AD
DDLM_End_Seq: OK,DS,NA,RS,RR,UE,TO,FE,RE,NI,SE,NE,AD,EA,LE,NC
Max_Len_Data_Unit:
The parameter Max_Len_Data_Unit defines the maximum possible length of the
parameter Data in the following Upload/Download frames.
Type: Unsigned8
Range: 1 to 240
9.4.3 Activate Parameter Set (unconfirmed)
After the Download of a parameter set this can be accepted and activated with
the function DDLM_Act_Para_Brct.
This function can be sent simultaneously to one (single) or many (multicast) DP-
Master (class 1) in dependence of the parameter Rem_Add.
In the operation modes Clear and Operate of the DP-Master (class 1) User-
Interface, the activation of the bus parameter set with changed FDL parameters
Baud_Rate or FDL_Add will not take place.
This function is not acknowledged by the receiver (reason: a possible change of
baud rate must take effect at all addressed DP-Masters nearly at the same time).