Page 734
PROFIBUS-Specification-Normative-Parts-8:1997
Copyright by PNO 1997 - all rights reserved
The time is calculated according to equation (8):
T
WD
in s = 10ms ⋅ WD_Fact_1 ⋅ WD_Fact_2 (8)
Times can be realized between 10ms and 650s independent of the baud
rate. The watchdog control is switched on or off by the bit WD_On.
Octet 4: Min. Station Delay Responder (min T
SDR
)
DP operation: Range: 0 to max T
SDR
(see table 7)
Mixed operation: Range: 0 to 255 t
Bit
This is the minimum waiting time for a DP-Slave until it is allowed to
send the response frames to the DP-Master. If in this octet 00H is
entered, the previous value remains unchanged.
Octet 5 to 6 (unsigned16): Ident_Number
The DP-Slave accepts only parameter frames if the transmitted
Ident_Number is identical with the own Ident_number. Exception: The
min T
SDR
is also allowed to be set if both bits Lock_Req and
Unlock_Req are zero and the Ident_Number is not identical.
Octet 7: Group_Ident
With this octet it is possible to build groups for the function
DDLM_Global_Control.
Each bit represents a group. The Group_Ident is only accepted if the
Lock_Req bit is set.
Octet 8 to 32: User_Prm_Data (extendible to 244, see section "Restrictions")
The following bytes are freely allocatable for DP-Slave specific
parameters, for Example diagnostic filter or regulator parameters. The
meaning and the ranges of values for the User_Prm_Data are defined
application specific.
Status:
The parameter Status indicates success or failure of the transfer.
Possible values: OK,DS,NA,RS,RR,UE,RE
9.3.5 Check Configuration Data
This function allows the DP-Master to deliver the configuration data to the DP-
Slave for checking. They contain the range of input and output areas as well as
the information about the data consistency as e. g. required for way setpoints
for positioning axis.
This consistency also affects DP-Slave and DP-Master (class 1). If a DP-Master
expects consistency of a DP-Slave data area, it reports this using the function
DDLM_Chk_Cfg with a set consistency bit. If the DP-Slave needs consistency for a
data area, it reports this using the function DDLM_Get_Cfg with a set
consistency bit. In this case the consistency bit for this data area of the DP-
Master shall also be set at the function DDLM_Chk_Cfg.
The DP-Slave compares its real configuration (Real_Cfg_Data) with the
configuration received from the DP-Master (Cfg_Data). When verifying the
configuration, the format and the length information as well the input/output
areas shall be identical. The verification of the consistency bit causes only in
the following cases a configuration fault (Diag.Cfg_Fault):
- The DP-Slave needs consistency for a data area and the DP-Master indicates no
consistency.
- The DP-Slave can not provide consistency for a data area and the DP-Master
requires consistency for this data area.