
Grounding and Safety
661
An IEEE Working Group (1972) stated that transformer saturation holds
down overvoltages based on transient network analyzer evaluations. But
others disagree. Field tests found that saturation did not lower the peak
voltage (Rajotte et al., 1995). A transformer core saturates when the flux is
highest. The flux is 90
∞
out of phase with the voltage. The peak flux occurs
when the voltage crosses through zero. So, when a transformer saturates, it
distorts the voltage but does not appreciably limit the peak voltage.
Normally, the highest overvoltages are for single line-to-ground faults, but
in some cases slightly higher overvoltages occur for double line-to-ground
faults. These cases normally involve large conductors (high
X/R
).
Spacer cable systems have higher overvoltages because of the messenger
wire (not because of the tighter phase and neutral spacings). An IEEE Work-
ing Group (1972) found overvoltages between 1.36 and 1.45 per unit with
spacer cable having a 5/16-in. or 3/8-in. copperweld messenger with a 30%
conductivity. If a spacer cable uses a lower-resistivity messenger or has a
separate neutral, overvoltages are similar to those of open-wire configura-
tions. ESEERCO (1992) simulated different spacer cable configurations and
found overvoltages of about 1.5 per unit on configurations with just a 3/8-
in. copperweld messenger. With a 1/0 ACSR neutral added to the spacer
cable, the overvoltages dropped to 1.3 per unit.
Underground cables normally have lower overvoltages. Rajotte et. al.
(1990) simulated overhead and underground systems and found that the
neutral shift was a factor of ten lower on underground systems. Urban
locations, whether overhead or underground, have many more grounds, so
overvoltages and other grounding issues such as stray voltage are less likely.
However, circuits of cables with tape shields or lead sheaths can have
significantly higher overvoltages. On these cables, the tape shields have very
high resistance. Figure 13.9 shows how the overvoltage on the unfaulted
phases increases with distance of the fault from the substation for an example
scenario. This example assumes that the sheath is perfectly grounded. If
poorly grounded, more current will return through the high-resistance sheath
and increase the overvoltage. Utilities normally use tape shield or lead
sheathed power cables in urban areas where distances are fortunately short.
The high resistance also contributes to transients; the
X/R
ratio is low enough
that faults often spark and cause transients at each zero crossing. In a resistive
circuit, when the arc clears at a zero crossing, the voltage builds up slowly,
which delays the arc breakdown. When the arc does restrike, a transient can
occur because of the trapped voltage just prior to the arc restrike.
13.2.2 Neutral Reactor
A reactor connected between the substation transformer neutral point and
the substation ground reduces ground fault currents. This limits duty on
equipment, but it reduces the effectiveness of the grounding system. During
line-to-ground faults, the voltages on the unfaulted phases are higher. A
1791_book.fm Page 661 Monday, August 4, 2003 3:20 PM
(C) 2004 by CRC Press LLC