All about Motors
Direct-on-line start of three-phase motors
Moeller Wiring Manual 02/05
8-30
8
Method of operation: Actuation of
pushbutton I energizes the coil of contactor
Q11. It switches on the motor running
clockwise and maintains itself after button I is
enabled via its own auxiliary contact
Q11/14-13 and pushbutton 0 (three-wire
control contact). The normally closed contact
Q11/22-21 electrically inhibits switch on of
contactor Q12. When pushbutton II is pressed,
contactor Q12 closes (the motor runs in the
anticlockwise direction). Depending on the
circuit, direction can be changed from
clockwise to anticlockwise either after
pressing pushbutton 0, or by directly pressing
the pushbutton for the reverse direction. In the
event of an overload, normally closed contact
95–96 of the overload relay F2 or normally
open contact 13–14 of the motor-protective
circuit-breaker or circuit-breaker will switch.
Reversing and two speeds (reversing contactor)
Special circuit (tapped winding) for feed
drives, etc.
FORWARD: feed or high speed
RETRACT: high speed only
STOP: tapped winding
1
5
3
L1
L3
L2
-F1
2
6
4
PE
M
3
-M1
97 95
98
96
1
5
3
2
6
4
1
5
3
2
6
4
2
6
4
2
6
4
2
6
4
1
5
3
-F2
97 95
98
96
-F21
-Q23
1U
1V
1W
2U
2V
2W
-Q17 -Q22 -Q21