G. Ziegler, 10/2005 page 244
Differential Protection Symposium
Belo HorizonteNovember 2005
Total fault current with a fault at the transformer HV terminals:
kA 19,23,74,211,3
MF
ΣI
GF
I
TF
IΣI =++=
−
+
−
+
−
=
F
Equivalent time constant:
ms 64
3.74.211.3
353.71004.26011.3
MF
ΣI
GF
I
TF
I
M
T
MF
ΣI
G
T
GF
I
T
T
TF
I
Equiv.
T =
++
⋅+⋅+⋅
=
−
+
−
+
−
⋅
−
+⋅
−
+⋅
−
=
As worst case, the CT 150/1 A in bay 1 is considered.
We consider a CT type 5P?, 30 VA, internal burden Pi= 15% (4.5 VA):
Connected burden Pa= 1 VA
CT over-dimensioning factor for 3ms saturation free time: K
TF
ca. 0.45
Corresponding to an overburdening factor of k
OB
= 1/K
TF
= 2.2
5845.0
150
200.19
' =⋅=⋅
−
Σ
=
TF
K
CTN
I
F
I
ALF
3.958
5.430
5.41
' =⋅
+
+
=⋅
+
+
= ALF
Pi
N
P
i
P
a
P
ALF
We finally choose: CT 5P10, 150/1, 30 VA, R2≤ 4.5 Ohm
Checking of the k-setting
(Stability with symmetrical fault currents):
()
5.0
12.24
2,2
14
=
−⋅
=
−⋅
>
OB
k
OB
k
k
(chosen: k=0.6)
CT dimensioning for busbarprotection 7SS5 and 7SS6, Example (2)