G. Ziegler, 10/2005 page 180
Differential Protection Symposium
Belo HorizonteNovember 2005
G
EB
∆I
T
I
K-G
I
K-T
∆I
T
7UT61
25 MVA
10,5 / 5 kV
F1
F2
Dimensioning of CTsat the station service transformer
Fault F1:
High fault currents in relation to the rated current
of the station-service transformer T2 (>100xI
N
)
and long DC time constants (>100 ms) require
considerable over-dimensioning of CT cores Œ
and • .
Fault F2:
uncritical as current is limited by short-circuit
impedance of station-service transformer T2.
CT Ž can have normal dimensions
Œ
•
250 MVA
220 /10 kV
250 MVA
10 kV
T2
T1
Ž