Belo HorizonteNovember 2005
Restricted earth fault protection 87N (7UT6)
Application aspects
n Increased sensitivity with earth faults near winding neutral
Preferably used in case of resistance or reactance neutral earthing
n Sensitive to turns short-circuit
n I0 / IN amplitude and angle comparison
n 2nd harmonic stabilised
n Can protect a separate shunt reactor or neutral earthingtransformer in
addition to the two winding transformer differential protection
n Not applicable with autotransformers! (as only one stabilising input at transformer
terminal side, --high impedance principle to be used in this case.