Ove Arup & Partners Consulting Engineers PC
Fire Safety in Theaters – A New Design Approach
Part I Assessment of Fire Safety Measures in Proscenium Theater
F:\06 PROJECTS\CURRENT PROJECTS\076040-49 THEATER PROJECT
DTX\REPORT\076040-49_THEATRE_R_20090910.DOC
Page
25/36
Ove Arup & Partners Consulting Engineers PC
10 September 2009
location. As the fire grew, the plume, however, started to impinge on the gallery and
contaminated more “fresh” air by traveling under the gallery. As a result, faster smoke
spread to the seating area was observed compared to Fire Scenario 3 (i.e., riggings),
but slower relative to Fire Scenario 1 (i.e., the center of a stage).
• The fastest system activations and slowest smoke spread to the seating area were
observed for Fire Scenario 3 (i.e., fire occurring in the riggings). This can be attributed
to: 1) the plume tended to carry all convective heat to ceiling level with minimal
disturbance and 2) a lesser amount of air was entrained to a plume due to the scenery
and the relatively short travel distance to a ceiling. As a result, a hotter and shallower
smoke layer was developed compared to the other scenarios.
• Rate-of-rise heat detectors were activated first among other devices such as sprinklers
and fusible links. As a result, a fire safety curtain is presumed to be activated by the
rate-of-rise heat detectors, prior to sprinkler activation.
• The CFD results show that in general ceiling-mounted rate-of-rise heat detectors
activate more rapidly than wall-mounted ones.
• It is not likely that a fire curtain would be activated by fusible links provided along the
fire safety curtain release line due to their slow thermal responses and that the
activation of sprinklers is estimated to occur earlier, potentially leading to cooling by
water spray of the fusible links.
• A plume generated from a fire originating at the center of a stage at floor level (i.e., Fire
Scenario 1) tends to lean toward the rear of a stage as air is drawn via the proscenium
opening, resulting in the faster predicted activation times near the back of the stage
(See Figure 19).
• Unless sprinklers at gridiron level are engulfed within a plume, sprinklers at ceiling level
are predicted to actuate prior to those at the gridiron sprinklers.
• The roof vents were not activated, prior to smoke spillage, except for the fires
originating in the riggings.
• For a fire occurring at the center of a stage in the large-sized theater, none of the fire
protection “devices” were activated until the heat release rate reached 22 MW. The
devices under consideration included three (3) rate-of-rise heat detectors located along
the proscenium wall above the proscenium opening. The devices were located in the
model based on direction received regarding common theater design practice.
Additional ceiling mounted rate-of-rise detectors were included in the model to evaluate
alternative optimal device locations, not commonly utilized in theater design. It was
found that these ceiling mounted devices responded more quickly than the proscenium
wall mounted devices, corresponding to a heat release rate less than 22 MW. The
findings suggest that ceiling mounted detection devices would potentially improve the
response time in deploying the stage fire safety systems (curtain and smoke vents) as
compared to the current common practice.
• Smoke was observed to spill to the seating area after approximately 250 seconds, well
prior to any automatic device actuation.