3.3 Factor ψ in Real Cases 37
3.3.4 Tube Bank with Various Passages of the External Fluid
We refer to the devices in Figs. 2.10 and 2.11. As already pointed out in Sect. 2.3.4,
the classic device of this kind is the heat recuperator located at the end of a steam
generator, provided that this type of exchanger can be used also with other fluids,
typically gaseous fluids.
The external fluid can enter the tube bank in correspondence of the entrance into
the tubes of the internal fluid, or the opposite takes place with the external fluid
entering the tube bank in correspondence of the exit from the tubes of the internal
fluid. Figure 2.10 represents a tube bank of the first kind with three passages of the
external fluid. Figure 2.11 represents a tube bank of the second kind instead.
Again, in the first case we speak of a tube bank with fluids in parallel flow, and
in the second case we speak of a tube bank with fluids in counter flow.
As for coils, we will refer to ψ
p
for the first type, and to ψ
c
for the second one
by introducing the usual corrective factors ϕ
p
and ϕ
c
.
This is the considered range: β = 0.1−3.0 e γ = 0.05−4.0
3.3.4.1 Tube Banks with Fluids in Parallel Flow
As far as the tube bank with fluids in parallel flow in Fig. 2.10, Tables B.31 and B.32
list t he values of ϕ
p
relative to 2 and 3 passages of the external fluid.
In Table B.31 the values of ϕ
p
are below unity for low values of β and γ .This
means that the heat transfer is greater than that corresponding to fluids in parallel
flow. Instead, for high values of β and γ the corrective factor is greater than unity.
For these values the behavior of the tube bank is worse compared to that of fluids in
parallel flow.
If the number of passages of the external fluid is equal to 3 instead (Table B.32)
the corrective factor ϕ
p
is always below unity, applies to a limited number of cases
and is generally close to unity.
Thus, it is possible to conclude that if the number of passages of the external fluid
is ≥ 3, the tube bank may be considered as actually having fluids in parallel flow
as far as the verification computation, thus neglecting the potential small advantage
represented by the fact that ϕ
p
< 1.
3.3.4.2 Tube Banks with Fluids in Counter Flow
Given the reference to fluids in counter flow the corrective factor in the tables is ϕ
c
.
Tables B.33, B.34 and B.35 are about tube banks with fluids in counter flow
shown in Fig. 2.11, respectively with 2, 3 and 4 passages of the external fluid.
We did not consider a higher number of passages because it is unlikely.
Note that the values of ϕ
c
are always above unity which means that the transferred
heat into tube bank is less than the one occurring with the fluids in actual counter
flow.