
//INTEGRAS/KCG/P AGIN ATION/ WILEY /WPS /FINALS_1 4-12- 04/0470855088_ 29_CHA28 .3D – 641 – [629–652/24]
17.12.2004 10:51PM
variable-speed wind turbines than for constant -speed wind turbines [Figure 28.3(a.ii)],
particularly if they are equipped with terminal voltage co ntrol. Further, it can be seen
that the rotor speed of the variable-speed turbine behaves more smoothly than that of a
constant-speed wind turbine. Variable-speed wind turbines do not have to be resyn-
chronised by the system, as is the case with constant-speed turbines. Rather, the con-
trollers of the variable-speed turbine control the rotor speed independent of the grid
frequency. Constant-speed turbines do not have such controllers. As mentioned earlier,
the exact behaviour of the rotor speed depends on the control strategy.
Voltage and rotor speed instability are not triggered only by faults. The tripping of a
synchronous generator from the grid may also result in a voltage drop that causes voltage
and rotor speed instability. Figures 28.4(a.i) and 28.4(a.ii) depict the rotor speed of a wind
farm with constant-speed turbines and the voltage at bus 32 when the synchronous
generator at bus 31 trips. Figures 28.4(b.i) and 28.4(b.ii) present the rotor speed and the
voltage at bus 32 for variable-speed turbines with (dotted line) and without (solid line)
terminal voltage or reactive power control. Figure 28.4 shows that constant-speed wind
turbines become unstable as a result of bus voltage decreases, whereas variable-speed
wind turbines stay connected. Further, it can be seen that wind turbines with terminal
voltage control behave more favourably than do wind turbines without voltage control,
because they attempt to bring the voltage back to its predisturbance value.
28.4.3.2 Response to a change in grid frequency
As discussed above, the mechanical and electrical behaviour of variable-speed wind
turbines is decoupled by power electronic converters. As a result, mechanical quantities,
such as rotor speed and mechanical power, are largely independent of electrical quan-
tities, such as active and reactive power and gen erator terminal voltage and frequency.
Therefore, the mechanical frequency of variable-speed wind turbines doe s not react to a
change in electrical grid frequency. The energy stored in the rotating mass of variable-
speed wind turbines is not released when the grid frequency drops. In practice, it is much
more likely that the frequency decreases than that it increases. To illustrate this effect,
the generators at buses 32, 36 and 37, generating 1750 MW, are replaced by wind farms.
This corresponds to a wind power penetration of about 28.5 %.
If wind turbines replace synchronous generators on such a large scale, the power from
the wind turbines has not only to replace the active power from the synchronous
generators but also to take on the other tasks carried out by the synchronous generators.
This refers mainly to the generation of reactive power and voltage control, as discussed
in Chapter 19. Otherwise, it will not be possible to keep the voltage at each bus within
the allowable deviation from its nominal value. The reason is that there are only limited
options for controlling the voltage if wind turbines replace conventional synchronous
generators. Therefore, this section studies only constant-speed wind turbi nes with SVCs,
and variable-speed wind turbines with terminal voltage controllers. Constant-speed
wind turbines without controllable reactive power source, and variable-speed wind
turbines running at unity power factor, are not taken into account: it is unreasonable
to look at the dynamic behaviour of a system that cannot be operated because of a lack
of voltage control possibilities.
Wind Power in Power Systems 641