80 CHAPTER 2 TRANSFORMERS
When two transformers are in parallel, we can vary the distribution of reactive
power between the transformers by adjusting the voltage-magnitude ratios.
When two paralleled transformers of equal kilovoltamperes do not share the
kilovoltamperes equally because their impedances dier, the kilovoltamperes
may be more nearly equalized by adjustment of the voltage-magnitude ratios
through tap changing.
Example 2.14. Repeat Example 2.13 except that Th includes hoth a transformer
having the same turns ratio as Ta a
n
d a regulating transformer with a phase shift
of 3
°
(t =