Electronic motor starters and drives
Connection examples, DM4
Moeller Wiring Manual 02/05
2-62
2
Delta connection
A delta connection allows the use of a soft starter
with a lower rating than the motor it is used to
control. Connected in series with each motor
winding, the current the soft starter needs to
supply is reduced by a factor of W3. This layout has
the drawback that six motor supply cables are
needed. Apart from that there are no restrictions.
All soft starter functions remain available.
For this you have to connect the motor in delta
and the voltage in this connection method must
agree with the mains voltage. For 400 V mains
voltage the motor must therefore be marked with
400 V/690 V.
Control section
n Emergency-Stop
S1: Off
S2: On
a Enable
b Soft start/Soft stop
E2: Enable
T1: +thermistor
T2: –thermistor
ab
S1
S2
K1
E1
39
E2
39
S4
S3
K1
K1
K2K1
Q11
K2
T1 K2 T1 Q11
T1 RUN
13
14
33
34
T1 OK
(no error)