Contactors and Relays
Control relay easy, Multi Function Display MFD-Titan®
Moeller Wiring Manual 02/05
5-55
5
Display text and actual values , display and edit set values
easy500 and easy700 can display 16, easy800 can
display 32 freely editable texts. In these texts
actual values of function relays such as, timer
relays, counters, hours run counters, anolog value
comparitors, dates, times or analog values can be
displayed. Set values of timer relays, counters,
hours run counters and analog value comparitors
can be altered during the display of the texts.
Example of a text display:
The text display has the following display
characteristics:
The text output unit D (D = Display,) functions in
the circuit diagram like a normal marker M.
Should a text be attached to a marker this would
be shown at condition 1 of the coil in the easy
display. A precondition is that the easy is in RUN
mode and before the texts are displayed the status
display is shown.
D1 is defined as alarm text and has therefore
priority over other displays.
D2 to D16/D32 are displayed when activated.
When several displays are activated they are
shown one after the other every 4 secs. When a
set value is edited the corresponding display
remains shown until the value transfer.
In one text several values, actual and set values,
from for example, function relays, analog input
values or times and dates can be combined. The
set values can be edited:
• easy500 and easy700, two values,
• easy800, four values.
SWITCHING;
CONTROL;
DISPLAY;
ALL EASY!
Line 1, 12 characters
Line 2, 12 characters, one actual value or set value
Line 3, 12 characters, one actual value or set value
Line 4, 12 characters
RUN TIME M:S
T1 :012:46
C1 :0355 ST
PRODUCED