G. Ziegler, 10/2005 page86
Differential Protection Symposium
Belo HorizonteNovember 2005
Proceed in the following steps:
1. Starting on the high voltage winding, the phase connection terminals are
numbered with 0, 4, 8 (always 4 x 30
O
= 120
O
phase shift).
2. The opposite end of each winding is labelled with a number incremented
by +6 relative to the phase connection (6x 30
O
=180
O
).
3. The secondary windings are numbered the same. In this context it is
assumed that the polarity of the windings is the same in the diagram. (If in
doubt, polarity marks may also be applied.)
4. The phase connection is labelled with the average value of the
corresponding terminal designations belonging to the winding terminals
connected to this phase terminal, e.g. (6+4)/2= 5
5. The difference between the high and low voltage side terminal numbers of
same phases corresponds each with the vector group number, beingYd5 in
this case.
Finding the vector group by using the clock principle