Table 13 — Minimum clearance guidelines for natural-draught operation
Minimum clearance
A B C D
Maximum heat
release per burner
Vertical to
centre-line roof
tubes or refractory
(vertical firing
only)
Horizontal from
burner centre-line
to wall tubes
centre-line
Horizontal from
burner centre-line
to unshielded
refractory
Between opposing
burners
(horizontal firing)
Burner
type
MW (Btu/h × 10
6
) m (ft) m (ft) m (ft) m (ft)
1,0 (3,41) 4,3 (14,1) 0,8 (2,6) 0,56 (1,9) 6,5 (21,4)
1,5 (5,12) 5,6 (18,5) 0,9 (3,0) 0,70 (2,3) 8,8 (29,0)
2,0 (6,8) 7,0 (22,9) 1,1 (3,5) 0,83 (2,7) 11,2 (36,7)
2,5 (8,5) 8,3 (27,4) 1,2 (3,9) 0,96 (3,1) 13,3 (43,6)
3,0 (10,2) 9,7 (31,8) 1,3 (4,3) 1,09 (3,6) 14,8 (48,7)
3,5 (11,9) 11,0 (36,2) 1,4 (4,7) 1,22 (4,0) 16,4 (53,8)
Oil-firing
4,0 (13,6) 12,4 (40,7) 1,6 (5,2) 1,35 (4,4) 18,0 (59,0)
0,5 (1,71) 2,6 (8,5) 0,6 (1,9) 0,44 (1,4) 3,4 (11,1)
1,0 (3,41) 3,6 (11,9) 0,7 (2,4) 0,56 (1,9) 4,9 (16,2)
1,5 (5,11) 4,6 (15,2) 0,8 (2,8) 0,70 (2,3) 6,5 (21,4)
2,0 (6,82) 5,6 (18,5) 1,0 (3,2) 0,83 (2,7) 8,1 (26,5)
2,5 (8,53) 6,7 (21,8) 1,1 (3,6) 0,96 (3,1) 9,6 (31,6)
3,0 (10,24) 7,7 (25,2) 1,2 (4,1) 1,09 (3,6) 11,1 (36,4)
3,5 (11,94) 8,7 (28,5) 1,4 (4,5) 1,22 (4,0) 11,9 (38,9)
4,0 (13,65) 9,7 (31,8) 1,5 (4,9) 1,35 (4,4) 12,6 (41,5)
4,5 (15,36) 10,7 (35,1) 1,6 (5,3) 1,48 (4,8) 13,4 (44,0)
Gas-firing
5,0 (17,06) 11,7 (38,5) 1,8 (5,7) 1,61 (5,3) 14,2 (46,6)
For horizontal firing, the distance between the burner centre-line and the roof tube centre-line or refractory shall be 50 %
greater than the distances in column B.
For combination liquid-and-gas burners, the clearances shall be based on liquid-fuel firing, except if liquid fuel is used for
start-up only.
For conventional gas burners, the longitudinal clearance may be decreased. This shall be achieved by multiplying
dimensions in column A by a factor of 0,77 and column D by a factor of 0,67.
For intermediate firing rates, the required clearances may be achieved by linear interpolation.
The clearances in column A and column D should be increased by 20 % for low NO
X
burners with NO
X
levels below
70 mg/m
3
(34 ppm by volume) based on a single burner with natural-gas firing, with 15 % excess ambient air and a
firebox temperature of 870 °C (1 600 °F).
NOTE Fuel-gas composition can affect the flame length.
ANSI/API Standard 560/ISO 13705